Clarks Size Calculator

Earth Size Calculator

Enter the line conductor size, and if you know them, the fault current, the disconnection time and how the earth is installed. The calculator gives the earth conductor size by the simple table and the adiabatic check.

  • Earth size
  • Table method
  • Adiabatic check
Your circuit

From 0.5 to 1000

From 0 to 100000

From 0.01 to 5

Fault current comes from the earth loop impedance at the far end of the circuit.

Up to 16 mm², the earth matches the line conductor. A 6 mm² circuit needs a 6 mm² earth by the simple table. With a 1,000 A fault cleared in 0.4 s, the adiabatic check needs 5.5 mm² at k = 115, so 6 mm² passes.

Earth conductor size chart

Copper, simple method. Search for a size.

Earth by line
Line (mm²)Earth (mm²)
1.51.5
2.52.5
44
66
1010
1616
2516
3516
5025
7035
9547.5
12060
15075
18592.5
240120

mm².

Line size and earth

Simple table. Slide the line size.

Both conductors are drawn to scale.

How to size an earth conductor

Line to earth. Step through it.

Line

Size.

Test continuity of every earth before energising.

Simple table or adiabatic check

Methods. Compare them.

Quick.

NeedsLine size only
ResultSafe, can be larger
UseMost circuits

The adiabatic check often allows a smaller earth than the table.

Before you install

Earthing checks. Tick each item.

Tick each item as you go.

Record test results on the installation certificate.

What you get

Earth sizing. Each tile explains one result.

Earth

mm².

Table

Method.

Adiabatic

Check.

Time

Disconnection.

k

Factor.

Twin and earth cable has a smaller earth than its line cores.

Frequently Asked Questions

What size earth cable do I need?

Up to sixteen square millimetres, the same as the line conductor.

What size earth for a twenty five mm² cable?

Sixteen square millimetres by the simple table.

What is the adiabatic equation?

Earth size equals the square root of fault current squared times time, divided by k.

What is k in the adiabatic equation?

A factor for the conductor and insulation, one hundred and fifteen for copper in PVC cable.

Is a smaller earth allowed?

Yes, if it passes the adiabatic check.

What size is the earth in two point five twin and earth?

One point five square millimetres.

Who should size earthing?

A qualified electrician, to your local wiring rules.

A safe path to earth

Size the earth conductor right and faults clear quickly and safely.

More size calculators

Each one has its own calculator, worked examples and answers to common questions.

See all size calculators