Enter the load in kW or amps, the power factor, the secondary voltage, single or three phase and how much growth to allow. The calculator gives the minimum kVA, the next standard size and its full load current.

  • kW or amps in
  • Standard kVA sizes
  • Full load current
Your load

From 0.01 to 100000

From 0.5 to 1

From 100 to 35000

Use the maximum demand you expect, not the sum of every nameplate, unless everything runs at once.

Transformers are rated in kVA, not kW. Divide the real load in kW by the power factor to get kVA, then add room for growth. A 100 kW load at power factor 0.85 with 20% growth needs about 141 kVA, so a 150 kVA transformer.

Transformer size chart

Power factor 0.85, 20% growth. Search for a load.

kVA by load
Load (kW)Needed (kVA)Standard size (kVA)
1014.115
2535.337.5
5070.675
100141.2150
200282.4300
400564.7750
8001129.41500

Standard sizes vary a little by region and maker.

Load and kVA

PF 0.85, 20% growth. Slide the load.

The gauge shows how heavily the standard size is loaded.

How to size a transformer

kW to kVA. Step through it.

Total the load

Maximum demand.

For three phase, current = kVA × 1000 ÷ (√3 × volts).

Dry type, oil filled or pad mounted

Transformer types. Compare them.

Air cooled, indoor.

SizesUp to about 3 MVA
Fire riskLow
UseBuildings

Indoor transformers are usually dry type for fire safety.

Before ordering

Spec checks. Tick each item.

Tick each item as you go.

Motor starting and welders draw large inrush currents. Check voltage dip as well as rating.

What you get

Transformer sizing. Each tile explains one result.

Minimum kVA

Load ÷ PF.

Standard size

Next up.

Full load amps

Secondary.

Loading

Today.

Growth

Allowed.

Running a transformer at 50% to 80% of rating is the most efficient and gives longer life.

Frequently Asked Questions

How do I size a transformer?

kVA = kW ÷ power factor, plus growth, then pick the next standard size.

What size transformer for 100 kW?

About 150 kVA at power factor 0.85 with 20% growth.

Why are transformers rated in kVA?

Their heating depends on current, whatever the power factor.

How do I convert amps to kVA?

Three phase: volts × amps × 1.732 ÷ 1000.

What is a standard transformer size?

Common sizes include 25, 50, 75, 100, 150, 300, 500, 750 and 1,000 kVA.

How much spare capacity should a transformer have?

About 20% to 25% for growth.

What is full load current?

The current at the rated kVA, which sizes the cables and breakers.