Clarks Size Calculator

MCB Size Calculator

Enter the load in kW, the supply voltage and phases, the power factor, the load type and the cable size. The calculator finds the design current, the next standard MCB rating and checks the cable.

  • MCB rating
  • Trip curve
  • Cable check
Your circuit

From 0.01 to 500

From 12 to 1000

From 0.3 to 1

Cable ratings here are for twin and earth clipped direct.

Ib = P ÷ V, then pick an MCB rated at or above it and no bigger than the cable. A 3 kW heater on 230 V draws 13 A, so a 16 A type B MCB suits it. A 2.5 mm² cable carrying about 27 A is fine.

MCB size chart

Single phase, 230 V. Search for a load.

MCB by load
LoadCurrentMCBCable
1 kW4.3 A6 A1.0 mm²
2 kW8.7 A10 A1.0 mm²
3 kW13 A16 A1.5 to 2.5 mm²
4.6 kW20 A20 A2.5 mm²
7 kW30.4 A32 A6 mm²
9.5 kW41.3 A50 A10 mm²
11 kW47.8 A50 A10 mm²

Amps.

Load and MCB

230 V single phase. Slide the load.

The MCB rating is shown on the breaker.

How to size an MCB

Load to breaker. Step through it.

Load

kW and power factor.

The breaker protects the cable, so never fit one bigger than the cable rating.

Type B, C or D

Trip curves. Compare them.

Homes.

Trips at3 to 5 × In
LoadsHeaters, sockets
InrushLow

Use C or D only where inrush currents trip a B.

Before you fit it

MCB checks. Tick each item.

Tick each item as you go.

Only a qualified electrician should fit or change breakers.

What you get

MCB sizing. Each tile explains one result.

Rating

Amps.

Curve

B, C or D.

Cable

Checked.

Current

Design.

Poles

Single or three.

An oversized MCB will not protect the cable from overheating.

Frequently Asked Questions

What size MCB do I need?

Work out the load current and pick the next standard rating above it.

What size MCB for a three kilowatt heater?

A sixteen amp type B breaker on two and a half square millimetre cable.

What is the difference between B and C type MCBs?

C types allow a bigger surge before tripping, for motors and lighting.

Can I fit a bigger MCB to stop it tripping?

No. The breaker must protect the cable, so find the cause instead.

What size MCB for an electric shower?

Often forty or forty five amps on ten square millimetre cable, check the shower rating.

Does cable length affect MCB size?

Long runs may need a bigger cable for voltage drop and fault current.

Protected circuits

Match the breaker to the load and the cable and the circuit stays safe.